数据中心气泵驱动复合冷却机组工作特性.

Authors :
周 峰
徐步青
薛连政
马国远
晏祥慧
Source :
Journal of Xi'an Polytechnic University. 2023, Vol. 37 Issue 5, p32-38. 7p.
Publication Year :
2023

Abstract

The booster-driven hybrid cooling unit using ambient energy for free cooling can work for a whole year as one unit and reduce the annual cooling energy consumption effectively in data centers. Two different type booster and its hybrid cooling units were developed and tested. The suction/discharge pressure and mass flow rate of two different boosters were studied under the annual temperature difference range. The performance and differences of two hybrid cooling units were analyzed. The results indicate that the suction/discharge pressure ratio of the large torque booster (No.1) is less than that of the small torque booster (No.2). In the test temperature difference range, the suction/discharge pressure ratio of No.1 booster decreases by 53.56%,which of No.2 booster decreases by 32.89%. The cooling capacity and energy efficiency ratio of No.1 booster-driven hybrid cooling unit (14.8 kW) is higher than that of No.2 booster unit(9.2 kW) at the same temperature difference(30℃) [ABSTRACT FROM AUTHOR]

Details

Language :
Chinese
ISSN :
1674649X
Volume :
37
Issue :
5
Database :
Academic Search Index
Journal :
Journal of Xi'an Polytechnic University
Publication Type :
Academic Journal
Accession number :
173421714
Full Text :
https://doi.org/10.13338/j.issn.1674-649x.2023.05.005