Numerical Simulation Study on Ventilation Effect in Utility Tunnel.
- Source :
-
Engineering Letters . Jun2024, Vol. 32 Issue 6, p1090-1096. 7p. - Publication Year :
- 2024
-
Abstract
- Urban utility tunnels have developed rapidly in recent years. The effective ventilation system maintains the air quality of the utility tunnel. In order to improve the ventilation performance of utility tunnel, a three-dimensional model of utility tunnel was established according to the design drawings. Based on Fluent 14.0 software, a flow model was established. And numerical simulation methods were used to study the optimization of air ducts and ventilation methods. The utility tunnel used top ventilation and interlayer ventilation. The ventilation methods of different ventilation areas of urban utility tunnels are compared. The results showed that the combination of operational gain and ventilation zone length mainly affected the ventilation effect. Based on the simulation results, a comprehensive ventilation mode consisting of top ventilation, natural ventilation at 400 m long entrance and mechanical outlet exhaust was proposed. Electric valve, fire door, exhaust fan and induction fan could be opened in the urban public utility tunnel at low speed. This new combination method is considered the optimal combination method for the maximum ventilation speed of urban utility tunnels. [ABSTRACT FROM AUTHOR]