Back to Search Start Over

Optimization Design Study of a Full-Range Charged Calibration Device for a Low-Voltage Current Transformer.

Authors :
Ding, Can
Feng, Tingting
Bai, Yaolong
Shi, Yiji
Source :
Energies (19961073). Jun2024, Vol. 17 Issue 11, p2496. 13p.
Publication Year :
2024

Abstract

According to standards, the harmonic content should be less than 5% at the time of calibration, while the calibration index proposed in this paper stipulates that the primary current amplitude of 1%~120% of the full range of the accuracy level reaches 0.05 S level. In view of the above problems and indexes, this paper adopts the active regulation technology of primary current; firstly, the harmonics of primary current are extracted, and then the opposite harmonic currents are injected by the penetrating wire to offset the harmonics, and finally, charged calibration is carried out. The inductive current transformer charged calibration device was first designed, and the particle swarm algorithm was used to optimize the offset performance of the key link of the background current offset suppression. The transfer function of the offset loop was derived, and it was theoretically analyzed that it can meet the offset requirements up to the 200th harmonic. The results show that the optimized calibration method can realize the full-range calibration of low-voltage inductive current transformers under charged conditions by making a prototype of the device and constructing a test circuit for experiments, and measuring the data and analyzing them. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
19961073
Volume :
17
Issue :
11
Database :
Academic Search Index
Journal :
Energies (19961073)
Publication Type :
Academic Journal
Accession number :
177858499
Full Text :
https://doi.org/10.3390/en17112496