Evaporation heat transfer and pressure drop of HFC-134a in a helically coiled concentric tube-in-tube heat exchanger

Authors :
Wongwises, Somchai
Polsongkram, Maitree
Source :
International Journal of Heat & Mass Transfer. Feb2006, Vol. 49 Issue 3/4, p658-670. 13p.
Publication Year :
2006

Abstract

Abstract: The two-phase heat transfer coefficient and pressure drop of HFC-134a during evaporation inside a smooth helically coiled concentric tube-in-tube heat exchanger are experimentally investigated. The test section is a 5.786-m long helically coiled tube with refrigerant flowing in the inner tube and heating water flowing in the annulus. The inner tube is made from copper tubing of 9.52mm outer diameter and 7.2mm inner diameter. The heat exchanger is fabricated by bending a straight copper tube into a spiral coil. The diameter of coil is 305mm. The test run are done at average saturated evaporating temperatures ranging between 10 and 20°C. The mass fluxes are between 400 and 800kgm−2 s−1 and the heat fluxes are between 5 and 10kWm−2. The inlet quality of the refrigerant in the test section is calculated using the temperature and pressure obtained from the experiment. The pressure drop across the test section is directly measured by a differential pressure transducer. The effects of heat flux, mass flux and, evaporation temperature on the heat transfer coefficients and pressure drop are also discussed. The results from the present experiment are compared with those obtained from the straight tube reported in the literature. New correlations for the convection heat transfer coefficient and pressure drop are proposed for practical applications. [Copyright &y& Elsevier]

Details

Language :
English
ISSN :
00179310
Volume :
49
Issue :
3/4
Database :
Academic Search Index
Journal :
International Journal of Heat & Mass Transfer
Publication Type :
Academic Journal
Accession number :
19591735
Full Text :
https://doi.org/10.1016/j.ijheatmasstransfer.2005.08.017