An Experimental Study of the Effects of Inlet Plenum Walls on Axial Fan Performance.

Authors :
Swim, William B.
Source :
ASHRAE Transactions. 2005, Vol. 111 Issue 1, p993-999. 7p.
Publication Year :
2005

Abstract

This experimental study determined the degradation in performance of large axial fans caused by close inlet walls. Three fans with hub to tip ratios of 0.39, 0.49. and 0.74 were each tested at four blade angles and over the flow rate range of wide open to near shutoff The closest walls, 0.5D front clearance and OD side clearance, caused only modest loss in flow rate, up to 3²%. and less than a 5% loss of efficiency in the 0.49 H/T fan. The other two fans had only minor decreases in flow rate and in efficiency for the closest walls. No significant losses were found for any of the test fans when tested with clearances larger than the minimum. [ABSTRACT FROM AUTHOR]