Impact of DG Interface Control on Islanding Detection and Nondetection Zones.

Authors :
Zeineldin, H. H.
El-Saadany, Ehab F.
Salama, M. M. A.
Source :
IEEE Transactions on Power Delivery. Jul2006, Vol. 21 Issue 3, p1515-1523. 9p. 2 Charts, 20 Graphs.
Publication Year :
2006

Abstract

Islanding detection of Distributed Generation (DG) is considered as one of the most important aspects when interconnecting DGs to the distribution system. With the increasing penetration and reliance of the distribution systems on DGs, new interface control strategies are being proposed. Aside from its main task of supplying active power, the DG could provide voltage support, improve the power factor, or mitigate other power quality problems. This paper examines the impact of the interface control strategy of inverter based DGs on islanding detection. The Non-detective Zone (NDZ) for over/under voltage and over/under frequency is derived analytically for each interface control and validated by simulation. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
21
Issue :
3
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
21582745
Full Text :
https://doi.org/10.1109/TPWRD.2005.858773