Negative-Sequence Current Injection for Fast Islanding Detection of a Distributed Resource Unit.
- Source :
-
IEEE Transactions on Power Electronics . Jan2008, Vol. 23 Issue 1, p298-307. 10p. 5 Diagrams, 1 Chart, 11 Graphs. - Publication Year :
- 2008
-
Abstract
- This paper presents an active islanding detection method for a distributed resource (DR) unit which is coupled to a utility grid through a three-phase voltage-sourced converter (VSC). The method is based on injecting a negative-sequence current through the VSC controller and detecting and quantifying the corresponding negative-sequence voltage at the point of common coupling of the VSC by means of a unified three-phase signal processor (UTSP). UTSP is an enhanced phase-locked loop system which provides high degree of immunity to noise, and thus enable islanding detection based on injecting a small (<3%) negative-sequence current. The negative-sequence current is injected by a negative-sequence controller which is adopted as the complementary of the conventional VSC current controller. Based on simulation studies in the PSCAD/EMTDC environment, performance of the islanding detection method under UL1741 anti-islanding test is evaluated, and its sensitivity to noise, grid short-circuit ratio, grid voltage imbalance, and deviations in the UL1741 test parameters are presented. The studies show that based on negative-sequence current injection of about 2% to 3%, islanding can be detected within 60 ms even for the worst case scenario. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 08858993
- Volume :
- 23
- Issue :
- 1
- Database :
- Academic Search Index
- Journal :
- IEEE Transactions on Power Electronics
- Publication Type :
- Academic Journal
- Accession number :
- 28437323
- Full Text :
- https://doi.org/10.1109/TPEL.2007.911774