Back to Search Start Over

Insulation Problems in Medium-Voltage Stator Coils Under Fast Repetitive Voltage Pulses.

Authors :
Ui Haq, Saeed
Jayaram, Shesha H.
Cherney, Edward A.
Source :
IEEE Transactions on Industry Applications. Jul/Aug2008, Vol. 44 Issue 4, p1004-1012. 9p. 5 Black and White Photographs, 7 Diagrams, 3 Charts, 5 Graphs.
Publication Year :
2008

Abstract

In this paper, the degradation processes in stator-bar groundwall insulation that is subjected to steep-front voltage pulses, at different temperatures, are studied. The test conditions include pulse voltage amplitudes up to 6 kVp and pulse switching frequencies up to 3 kHz in ambient temperatures of 23°C, 120 °C, and 155 ° C. During the aging process, the surface temperature is monitored with an infrared camera to determine the regions with highest temperatures and the partial discharge (PD) activity. The visual examination of failed bars confirmed that the groundwall insulation in these regions is degraded. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00939994
Volume :
44
Issue :
4
Database :
Academic Search Index
Journal :
IEEE Transactions on Industry Applications
Publication Type :
Academic Journal
Accession number :
34264055
Full Text :
https://doi.org/10.1109/TIA.2008.926305