Hailian Xie
Angquist, Lennart
Nee, Hans-Peter
Source :
IEEE Transactions on Power Systems. Nov2008, Vol. 23 Issue 4, p1653-1661. 9p. 3 Black and White Photographs, 4 Diagrams, 8 Charts, 11 Graphs.
Publication Year :
2008

Abstract

A transformer might be driven into saturation by faults in the connected system. In a transmission system with a Static synchronous Compensator and transformers connected at the point of common coupling, different modulation schemes utilized by the voltage source converter influence the transformer saturation in different ways. This paper compares the saturation effect during fault recovery when two alternative modulation schemes are utilized: voltage modulation and flux modulation. The comparison shows that utilization of flux modulation scheme tends to soften the saturation problem during fault recovery. However, this is achieved at a higher converter transient peak current. [ABSTRACT FROM AUTHOR]