Back to Search Start Over

Adaptive Prony Method for the Calculation of Power-Quality Indices in the Presence of Nonstationary Disturbance Waveforms.

Authors :
Andreotti, A.
Bracale, A.
Caramia, P.
Carpinelli, G.
Source :
IEEE Transactions on Power Delivery. Apr2009, Vol. 24 Issue 2, p874-883. 10p. 3 Charts, 19 Graphs.
Publication Year :
2009

Abstract

The presence of the new liberalized markets has increased the interest in power-quality (PQ) disturbances due to their economic effect. In particular, in the case of disturbances caused by a single event (such as a capacitor switching or voltage sag), the waveform assessment can be difficult due to the rapid variations in waveform spectral component characteristics; these difficulties require a suitable choice of signal-processing techniques for spectral analysis and, in particular, the resort to time-frequency representations. In this paper, the adaptive Prony method is proposed to calculate PQ indices based on a time-frequency analysis of waveforms. Numerical applications on a simulated transient due to capacitor switching, a measured voltage sag, and a test waveform are also presented and discussed in order to investigate the validity of the proposed method. [ABSTRACT FROM AUTHOR]