- Source :
-
IEEE Transactions on Electromagnetic Compatibility . May2009, Vol. 51 Issue 2, p236-244. 9p. 5 Black and White Photographs, 5 Diagrams, 5 Graphs. - Publication Year :
- 2009
-
Abstract
- Wideband frequency electromagnetic (EM) noise generated during the turn-ON and turn-OFF processes of thyristor valves in converter stations is conducted along the primary circuitry, and may interfere with secondary systems. The EM interference (EMI) problem in a ±800 kV ultra-HVdc converter station is an important issue that should be studied carefully in the design stage. A method to analyze the conducted EM disturbance (EMD) based on time-domain wideband circuit simulation is proposed here, which is verified through the field test results of a ±500 kV converter station. Models of major equipment are described. The EMD levels of a ±800 kV converter station, which is currently being planned and built in China, are calculated, and compared with those of a ±500 kV converter station. [ABSTRACT FROM AUTHOR]