Back to Search
Start Over
A new current balancer in single-phase three-wire secondary distribution feeders using the correlation coefficients.
- Source :
-
Electrical Engineering in Japan . Oct2009, Vol. 169 Issue 1, p50-58. 9p. 3 Diagrams, 4 Charts, 4 Graphs. - Publication Year :
- 2009
-
Abstract
- This paper proposes a new current balancer in single-phase three-wire secondary distribution systems using the correlation coefficients. The components of the load currents correlative to the primary side voltage waveform, which correspond to the active currents, are detected in each feeder, then the nonactive and unbalanced-active components are compensated on the source side. The balanced currents with unity power factor are obtained in each feeder. The basic principle of the proposed method is discussed in detail, and then confirmed by digital computer simulation. A prototype experimental system is constructed and tested. Experimental results demonstrate that the balanced source currents with unity power factor are obtained in spite of unbalanced load currents. © 2009 Wiley Periodicals, Inc. Electr Eng Jpn, 169(1): 50–58, 2009; Published online in Wiley InterScience (<URL>www.interscience.wiley.com</URL>). DOI 10.1002/eej.20843 [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 04247760
- Volume :
- 169
- Issue :
- 1
- Database :
- Academic Search Index
- Journal :
- Electrical Engineering in Japan
- Publication Type :
- Academic Journal
- Accession number :
- 42421621
- Full Text :
- https://doi.org/10.1002/eej.20843