Back to Search Start Over

Chiller sequencing control with enhanced robustness for energy efficient operation

Authors :
Sun, Yongjun
Wang, Shengwei
Huang, Gongsheng
Source :
Energy & Buildings. Nov2009, Vol. 41 Issue 11, p1246-1255. 10p.
Publication Year :
2009

Abstract

Abstract: This paper presents a strategy for improving the reliability and the energy efficiency of chiller sequencing control based on the total cooling load measurement of centralized multiple centrifugal chiller plants. The improvement is achieved as follows. Firstly, a fused measurement of building cooling load is used to replace the direct/indirect measurement. Secondly, the maximum cooling capacity of individual chillers is computed online using a simplified centrifugal chiller model. Thirdly, the online computed maximum cooling capacity is calibrated according to the quality of the fused measurement in order to deal with the possible misbehaviours in measurement instruments. A simplified model for computing the maximum cooling capacity is developed and validated using field data. The performance of the proposed chiller sequencing control strategy is tested and compared with a conventional chiller sequencing control algorithm. Test results are presented showing that the proposed strategy can effectively improve the reliability of chiller sequencing control and reduce the energy consumption of chiller plants. [Copyright &y& Elsevier]

Details

Language :
English
ISSN :
03787788
Volume :
41
Issue :
11
Database :
Academic Search Index
Journal :
Energy & Buildings
Publication Type :
Academic Journal
Accession number :
44118285
Full Text :
https://doi.org/10.1016/j.enbuild.2009.07.023