Back to Search Start Over

Harmonic Power Standard at NIM and Its Compensation Algorithm.

Authors :
Lu Zuliang
Wang Lei
Li Mi Liu Lijuan
Zhou Hao
Source :
IEEE Transactions on Instrumentation & Measurement. Jan2010, Vol. 59 Issue 1, p180-187. 8p. 1 Diagram, 6 Charts, 1 Graph.
Publication Year :
2010

Abstract

A new harmonic power standard has been developed at the National Institute of Metrology (NIM), Beijing, China, for the calibration of harmonic power analyzers under nonsinusoidal conditions at fundamental frequencies of 50 and 60 Hz. The standard is based on digital sampling techniques that do not require synchronization. A compensation algorithm is presented in this paper. A new definition of the uncertainty for harmonic measurement is proposed that is referred to the fundamental. A characterization signal and its application are introduced. Results have shown that over its operating range of up to 50 A, 500 V, and the sixtieth-order harmonic, the harmonic power standard has uncertainties (k = 2) of less than 30 μV/V, 36 μA/A, and 42 μW/VA for voltage, current, and power measurements, respectively. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00189456
Volume :
59
Issue :
1
Database :
Academic Search Index
Journal :
IEEE Transactions on Instrumentation & Measurement
Publication Type :
Academic Journal
Accession number :
47838363
Full Text :
https://doi.org/10.1109/TIM.2009.2022446