Back to Search Start Over

Development of Arc-Guided Protection Devices Against Lightning Breakage of Covered Conductors on Distribution Lines.

Authors :
Weijiang Chen
Shanqiang Gu
Jinhiang He
Bin Yin
Source :
IEEE Transactions on Power Delivery. Jan2010, Vol. 25 Issue 1, p196-205. 10p. 5 Black and White Photographs, 19 Diagrams, 3 Charts.
Publication Year :
2010

Abstract

The breakage of overhead covered conductors on distribution lines resulting from the short-circuit arcs caused by lightning flash becomes a challenge as the application of covered conductors increases on distribution lines. Based on various methodologies and devices developed to avoid the covered conductor breakage in the world, novel arc-guided devices, including arcing protection hardware with barbs, clamping post composite insulator, and barb electrode clamping post porcelain/composite insulator are presented in this paper. Experimental results are also presented to validate these new developed devices. Devices based on the developed technologies have been widely applied on the power grids in China successfully. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
25
Issue :
1
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
48285922
Full Text :
https://doi.org/10.1109/TPWRD.2009.2033970