Abstract

For distribution lines in Japan, protection measures against lightning-induced overvoltages have been taken and can be considered almost complete. The focus of lightning protection measures has moved to overvoltages due to direct lightning strokes. Studies of such overvoltages require simulations using the EMTP (Electro-Magnetic Transients Program), and components of a distribution line must be modeled appropriately in the EMTP simulation environment. The authors have proposed an EMTP model of a distribution line in a separate paper. This paper consists of two parts. The first part presents surge characteristics of a distribution line obtained by measurement using an actual-scale test distribution line. In particular, the result reveals noteworthy characteristics of the surge impedance of a reinforced concrete pole and the wavefront-time dependence of insulator voltages. The second part presents a validation of the distribution line model previously proposed by the authors. The validation shows that the distribution line model accurately reproduces the measured voltage and current waveforms for various wavefront times of the injected currents. © 2010 Wiley Periodicals, Inc. Electr Eng Jpn, 173(1): 1–10, 2010; Published online in Wiley InterScience (<URL>www.interscience.wiley.com</URL>). DOI 10.1002/eej.21002 [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
04247760
Volume :
173
Issue :
1
Database :
Academic Search Index
Journal :
Electrical Engineering in Japan
Publication Type :
Academic Journal
Accession number :
51662087
Full Text :
https://doi.org/10.1002/eej.21002