Fuzzy-logic-based fault classification scheme for digital distance protection.

Authors :
Das, Biswarup
Reddy, J. Vittal
Source :
IEEE Transactions on Power Delivery. Apr2005 Part 1, Vol. 20 Issue 2, p609-616. 8p. 4 Diagrams, 14 Charts.
Publication Year :
2005

Abstract

In this paper, a fuzzy-logic-based algorithm to identify the type of faults for digital distance protection system has been developed. The proposed technique is able to accurately identify the phase(s) involved in all ten types of shunt faults that may occur in a transmission line under different fault resistances, inception angle, and loading levels. The proposed method needs only three line-current measurements available at the relay location and can perform the fault classification task in about a half-cycle period. Thus, the proposed technique is well suited for implementation in a digital distance protection scheme. [ABSTRACT FROM PUBLISHER]