Back to Search Start Over

Investigation on digital algorithm for on-line monitoring and diagnostics of metal oxide surge arrester based on an accurate model.

Authors :
Tong Zhao
Qingmin Li
Jiali Qian
Source :
IEEE Transactions on Power Delivery. Apr2005 Part 1, Vol. 20 Issue 2, p751-756. 6p. 3 Diagrams, 2 Charts, 5 Graphs.
Publication Year :
2005

Abstract

The digital algorithms presently available for on-line monitoring of metal oxide surge arrester (MOA) are normally based on a simplified equivalent model consisting of a capacitor and a nonlinear resistor in parallel, which however in applications poses some deficiency compared with experimental results, leading to a certain phase discrepancy between the line voltage and the resistive branch current, due to a capacitive effect in the branch. This paper develops a new digital algorithm based on an accurate model of metal oxide surge arrester, in which base-frequency approximating method and iterating scheme are combined in use. Computer simulations are carried out to validate the new approach, showing the digital algorithm gives an application accuracy of less than 1% even with harmonised power source and different levels of background noises while within 10% of the measured sum leakage current. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858977
Volume :
20
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
52037700
Full Text :