Hilbert transform based control algorithm of the DG interface for voltage flicker mitigation.

Authors :
Marei, Mostafa I.
Abdel-Galil, Tarek K.
El-Saadany, Ehab F.
Salama, Magdy M. A.
Source :
IEEE Transactions on Power Delivery. Apr2005 Part 1, Vol. 20 Issue 2, p1129-1133. 5p. 3 Diagrams, 4 Graphs.
Publication Year :
2005

Abstract

Distributed Generation (DG) is used widely in the modern distribution systems. This paper proposes a novel functionality of the interface between DG and the utility network to mitigate the voltage flicker and to regulate the voltage at the Point of Common Coupling (PCC) in addition to its main function of controlling the power flow. A new control algorithm for the DG interface based on the Hilbert transform (HT) is presented. The HT is employed as an effective technique for tracking the voltage flicker levels in distribution systems. The mathematical simplicity of the proposed technique, compared with the commonly used algorithms in the literature, renders them competitive candidates for the on-line tracking of voltage flicker. The accurate tracking of the HT facilitates its implementation for the control of flicker mitigation devices. Simulation results are provided to verify the tracking capabilities of the HT and to evaluate the performance of the proposed DG interface for multifunction operation. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858977
Volume :
20
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
52037749
Full Text :
https://doi.org/10.1109/TPWRD.2004.843461