Back to Search Start Over

Analysis of a Commercial Wind Farm in Taiwan Part I: Measurement Results and Simulations.

Authors :
Wang, Li
Yeh, Tai-Her
Lee, Wei-Jen
Chen, Zhe
Source :
IEEE Transactions on Industry Applications. 03/01/2011, Vol. 47 Issue 2, p939-953. 15p.
Publication Year :
2011

Abstract

This paper presents both steady-state performance and dynamic simulations of a commercial wind farm (WF) in Taiwan through field measurement results and computer simulations. The companion paper in Part II discusses the dynamic and transient analyzed results of using current-limit reactors (CLRs) and load tap changers on power-quality improvement of the studied WF. With 23 2-MW DFIG-type wind turbine generators, this WF is connected to the 161-kV extra high-voltage substation of Taiwan Power System through a 23/161-kV 60-MVA step-up main transformer from six feeders with CLRs. Through comparing field measured results, this paper establishes a simulation model to simulate and analyze the steady-state and dynamic characteristics of the studied WF which is subject to disturbance conditions under different wind-speed conditions. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
00939994
Volume :
47
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Industry Applications
Publication Type :
Academic Journal
Accession number :
59470778
Full Text :
https://doi.org/10.1109/TIA.2010.2101991