Back to Search Start Over

Implementation and Performance Evaluation of a Reclosing Method for Shunt Reactor-Compensated Transmission Lines.

Authors :
Mestas, Patricia
Tavares, Maria Cristina
Gole, Aniruddha M.
Source :
IEEE Transactions on Power Delivery. 04/01/2011, Vol. 26 Issue 2, p954-962. 9p.
Publication Year :
2011

Abstract

This paper proposes a new control method to reduce overvoltages due to three-phase reclosing for shunt compensated transmission lines (TL). The method detects the first minimum voltage region of the beating across the circuit breakers after protection dead time and works independently of voltage zero crossing, reducing significantly the reclosure time. The controller was tested on a Real Time Digital Simulator (RTDS) and its performance was compared to the traditional preinsertion resistor approach and another existing control method. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
26
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
59569129
Full Text :
https://doi.org/10.1109/TPWRD.2010.2084111