- This paper proposes voltage-shift acceleration control for islanding detection of distributed-generation (DG) inverters. The proposed method is conceptually based on a traditional dq-based voltage positive feedback control. A main improvement of the proposed control is that the anti-islanding performance and its impact on inverter output control can be consistent regardless of inverter operation points. An analytical approach based on a small-signal model of an inverter controller is used to prove the proposed control. Also, an analytical design method is proposed to obtain proper control gain that satisfies two conflicting issues: successful anti-islanding and limited impact on inverter control. Simulation and experimental tests were conducted to validate the proposed detection algorithm and its design method. In addition, simulation results on a two DGs system are shown to investigate the performance in multiple DGs operation. [ABSTRACT FROM AUTHOR]