Back to Search
Start Over
Correlations for evaporation heat transfer coefficient and two-phase friction factor for R-134a flowing through horizontal corrugated tubes
- Source :
-
International Communications in Heat & Mass Transfer . Dec2011, Vol. 38 Issue 10, p1406-1413. 8p. - Publication Year :
- 2011
-
Abstract
- Abstract: Correlations for the evaporation heat transfer coefficient and two-phase friction factor of R-134a flowing through horizontal corrugated tubes are proposed. In the present study, the test section is a horizontal counter-flow concentric tube-in-tube heat exchanger with R-134a flowing in the inner tube and hot water flowing in the annulus. Smooth tube and corrugated tubes with inner diameters of 8.7mm and lengths of 2000mm are used as the inner tube. The corrugation pitches are 5.08, 6.35, and 8.46mm and the corrugation depths are 1, 1.25, and 1.5mm, respectively. The outer tube is made from smooth copper tube with an inner diameter of 21.2mm. The correlations presented are formed by using approximately 200 data points for five different corrugated tube geometries and are then proposed in terms of Nusselt number, equivalent Reynolds number, Prandtl number, corrugation pitch and depth, and inside diameter. [Copyright &y& Elsevier]
Details
- Language :
- English
- ISSN :
- 07351933
- Volume :
- 38
- Issue :
- 10
- Database :
- Academic Search Index
- Journal :
- International Communications in Heat & Mass Transfer
- Publication Type :
- Academic Journal
- Accession number :
- 67248759
- Full Text :
- https://doi.org/10.1016/j.icheatmasstransfer.2011.08.014