Back to Search Start Over

Lightning back flashover double circuit tripping pattern of 132kV lines in Malaysia

Authors :
Bakar, A.H.A.
Talib, D.N.A.
Mokhlis, H.
Illias, H.A.
Source :
International Journal of Electrical Power & Energy Systems. Feb2013, Vol. 45 Issue 1, p235-241. 7p.
Publication Year :
2013

Abstract

Abstract: This paper presents a study on flashover patterns due to double tripping using EMTP software. The simulation was performed on a 132kV line double circuit for economic installation of transmission line arresters (TLAs). The simulation results were validated with the field data of 132kV transmission line in Malaysia. A vertically configured double circuit transmission line was modelled and the effects of tower footing resistance, lighting current values, power frequency voltage and the coupling effect of the phase conductors study were taken into account. A good agreement between the simulation and field data was obtained. A specific back flashover phase of the double circuit line can be determined by considering the effects that have been mentioned. Through determination of the tripping pattern, a suitable installation of line arresters and mitigation of line tripping due to back flashover can be achieved. [Copyright &y& Elsevier]

Details

Language :
English
ISSN :
01420615
Volume :
45
Issue :
1
Database :
Academic Search Index
Journal :
International Journal of Electrical Power & Energy Systems
Publication Type :
Academic Journal
Accession number :
83871344
Full Text :
https://doi.org/10.1016/j.ijepes.2012.08.048