‘Derating Factor’ new concept for evaluating thermal performance of earth air tunnel heat exchanger: A transient CFD analysis

Authors :
Bansal, Vikas
Misra, Rohit
Agarwal, Ghanshyam Das
Mathur, Jyotirmay
Source :
Applied Energy. Feb2013, Vol. 102, p418-426. 9p.
Publication Year :
2013

Abstract

Abstract: A new term ‘Derating Factor’ is devised for evaluating deterioration in thermal performance of Earth Air Tunnel Heat Exchanger (EATHE) under transient operating conditions in predominantly hot and dry climate of Ajmer (India) using experimental and computational fluid dynamics modeling with FLUENT software. Maximum air temperature drop obtained using steady state approach for EATHE of pipe length 100m, pipe diameter 0.2m and at air velocity of 5ms−1 is 18.4°C, 18.7°C and 18.4°C for soil thermal conductivity of 0.52, 2.0 and 4.0Wm−1 K−1 respectively. However, the maximum air temperature drop obtained using transient approach during 24h of operation vary between 18.3°C and 14.0°C, 18.3°C and 17.2°C and 18.6°C and 18.0°C for soil thermal conductivity of 0.52, 2.0 and 4.0Wm−1 K−1 respectively. The derating factor is found to be a function of thermal conductivity of soil, duration of continuous operation of EATHE and length of pipe. The analyzed cases have shown the range of derating to be as minimal as 0.2% to as high as 68%, which if ignored while designing may lead to poor performance of earth air heat exchangers. Maximum value of derating factor is observed after continuous operation of EATHE for 24h. [Copyright &y& Elsevier]

Details

Language :
English
ISSN :
03062619
Volume :
102
Database :
Academic Search Index
Journal :
Applied Energy
Publication Type :
Academic Journal
Accession number :
83933780
Full Text :
https://doi.org/10.1016/j.apenergy.2012.07.027