Back to Search Start Over

Full-Feedforward Schemes of Grid Voltages for a Three-Phase LCL-Type Grid-Connected Inverter.

Authors :
Li, Weiwei
Ruan, Xinbo
Pan, Donghua
Wang, Xuehua
Source :
IEEE Transactions on Industrial Electronics. Jun2013, Vol. 60 Issue 6, p2237-2250. 14p.
Publication Year :
2013

Abstract

This paper investigates the feedforward schemes of grid voltages for a three-phase LCL-type grid-connected inverter. The full-feedforward functions of grid voltages are derived for the stationary \alpha - \beta frame, synchronous d - q frame, and decoupled synchronous d - q frame-controlled three-phase LCL-type grid-connected inverters. The derived full-feedforward functions mainly consist of three parts which are proportional, derivative, and second derivative parts. The use of the traditional proportional feedforward function in the three-phase LCL-type grid-connected inverter will result in the amplification of the high-frequency injected grid current harmonics. With the proposed full-feedforward schemes, the injected grid current harmonics and unbalance caused by grid voltages can be greatly reduced. The effectiveness of the proposed feedforward schemes is verified by the experimental results. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
02780046
Volume :
60
Issue :
6
Database :
Academic Search Index
Journal :
IEEE Transactions on Industrial Electronics
Publication Type :
Academic Journal
Accession number :
85358435
Full Text :