Full-Feedforward Schemes of Grid Voltages for a Three-Phase LCL-Type Grid-Connected Inverter.
- Source :
-
IEEE Transactions on Industrial Electronics . Jun2013, Vol. 60 Issue 6, p2237-2250. 14p. - Publication Year :
- 2013
-
Abstract
- This paper investigates the feedforward schemes of grid voltages for a three-phase LCL-type grid-connected inverter. The full-feedforward functions of grid voltages are derived for the stationary \alpha - \beta frame, synchronous d - q frame, and decoupled synchronous d - q frame-controlled three-phase LCL-type grid-connected inverters. The derived full-feedforward functions mainly consist of three parts which are proportional, derivative, and second derivative parts. The use of the traditional proportional feedforward function in the three-phase LCL-type grid-connected inverter will result in the amplification of the high-frequency injected grid current harmonics. With the proposed full-feedforward schemes, the injected grid current harmonics and unbalance caused by grid voltages can be greatly reduced. The effectiveness of the proposed feedforward schemes is verified by the experimental results. [ABSTRACT FROM PUBLISHER]
Details
- Language :
- English
- ISSN :
- 02780046
- Volume :
- 60
- Issue :
- 6
- Database :
- Academic Search Index
- Journal :
- IEEE Transactions on Industrial Electronics
- Publication Type :
- Academic Journal
- Accession number :
- 85358435
- Full Text :
- https://doi.org/10.1109/TIE.2012.2193864