StatCom control at wind farms with fixed-speed induction generators under asymmetrical grid faults.

Authors :
Wessels, Christian
Hoffmann, Nils
Molinas, Marta
Fuchs, Friedrich Wilhelm
Source :
IEEE Transactions on Industrial Electronics. Jul2013, Vol. 60 Issue 7, p2864-2873. 10p.
Publication Year :
2013

Abstract

The stability of fixed-speed induction generator (FSIG)-based wind turbines can be improved by a StatCom, which is well known and documented in the literature for balanced grid voltage dips. Under unbalanced grid voltage dips, the negative-sequence voltage causes heavy generator torque oscillations that reduce the lifetime of the drive train. In this paper, investigations on an FSIG-based wind farm in combination with a StatCom under unbalanced grid voltage fault are carried out by means of theory, simulations, and measurements. A StatCom control structure with the capability to coordinate the control between the positive and the negative sequence of the grid voltage is proposed. The results clarify the effect of the positive- and the negative-sequence voltage compensation by a StatCom on the operation of the FSIG-based wind farm. With first priority, the StatCom ensures the maximum fault-ride-through enhancement of the wind farm by compensating the positive-sequence voltage. The remaining StatCom current capability of the StatCom is controlled to compensate the negative-sequence voltage, in order to reduce the torque oscillations. The theoretical analyses are verified by simulations and measurement results on a 22-kW laboratory setup. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
02780046
Volume :
60
Issue :
7
Database :
Academic Search Index
Journal :
IEEE Transactions on Industrial Electronics
Publication Type :
Academic Journal
Accession number :
85988294
Full Text :
https://doi.org/10.1109/TIE.2012.2233694