Studies on the Stator Single-Phase-to-Ground Fault Protection for a High-Voltage Cable-Wound Generator.

Authors :
Wang, Yuan Yuan
Zeng, Xiang Jun
Jian, Jin Bao
Dong, Zhao Yang
Li, Ze Wen
Huang, Yue
Source :
IEEE Transactions on Energy Conversion. Jun2013, Vol. 28 Issue 2, p344-352. 9p.
Publication Year :
2013

Abstract

A new criterion to detect the stator single-phase-to-ground fault for Powerformer is proposed in this paper, which is based on the direction of leakage currents, magnitude of leakage currents, and fault point energy dissipation. New fault characteristics of Powerformer are analyzed and a novel criterion is put forward. The proposed approach detects the ground fault by analyzing the direction, magnitude, and energy of leakage current, which is the difference of zero-sequence current fault component between the neutral and the terminal of Powerformer. The fundamental component and the third-harmonic component of leakage current are combined to realize 100% coverage of fault detection for the stator windings of Powerformer. Simulation results have shown that, under different fault conditions, the new scheme can distinguish internal faults from external faults reliably, and can detect in which machine a stator single-phase-to-ground fault is occurring even if the fault resistance is at 5 kΩ. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858969
Volume :
28
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Energy Conversion
Publication Type :
Academic Journal
Accession number :
87618132
Full Text :
https://doi.org/10.1109/TEC.2013.2240303