Back to Search Start Over

Optimum operating performance based online fault-tolerant control strategy for sensor faults in air conditioning systems.

Authors :
Yang, Xue-Bin
Jin, Xin-Qiao
Du, Zhi-Min
Fan, Bo
Zhu, Yong-Hua
Source :
Automation in Construction. Jan2014, Vol. 37, p145-154. 10p.
Publication Year :
2014

Abstract

Abstract: This paper presents an online fault-tolerant control strategy. By correcting the faulty measurements with a final correcting factor, the strategy covers five steps: fault detection, construction of correcting alternatives, performance forecasting, alternatives outranking, and fault correction. System energy, indoor air quality, human thermal comfort, and control efficiency are considered as a whole to evaluate the operating performance. Taking the supply air temperature sensor faults as testing examples, the strategy is tested in a virtual air conditioning system and simulated on TRNSYS platform. The testing results show that a large fault correcting factor is obtained in the first hour, an adjusting phase presents in the next several hours, and the correction factor keeps unchanged finally. High level of calculating accuracy is required for the performance prediction model. Also, for the outranking evaluation model, the thresholds and weight coefficients should be assigned appropriately to meet the requirements of building functions and/or owners. [Copyright &y& Elsevier]

Details

Language :
English
ISSN :
09265805
Volume :
37
Database :
Academic Search Index
Journal :
Automation in Construction
Publication Type :
Academic Journal
Accession number :
92730368
Full Text :
https://doi.org/10.1016/j.autcon.2013.10.011