Back to Search Start Over

Arc-Flash Hazard Calculations in LV and MV DC Systems—Part I: Short-Circuit Calculations.

Authors :
Das, J. C.
Source :
IEEE Transactions on Industry Applications. May2014, Vol. 50 Issue 3, p1687-1697. 11p.
Publication Year :
2014

Abstract

The IEEE 1584 Guide does not address arc-flash hazard in dc systems. The interest in this subject is evidenced by current publications. The National Fire Protection Association (NFPA) 2012 methodology has added a small description of the calculations of arc-flash hazard in dc systems. However, there are serious inaccuracies in the application of the methodology that is advocated in the NFPA. A review of the current literature indicates that there is no comprehensive document on the subject and that some of the assumptions made in the current literature are not accurate, e.g., with respect to the short-circuit current profiles and protective devices in dc systems, which are very fundamental to the accurate calculations of arc-flash hazard in dc systems. This paper is presented in two parts. This part provides equations with practical examples of short-circuit calculations in dc systems. The second part provides the analysis of arc-flash hazard. Accurate calculations of the short-circuit currents and ascertaining their profiles is the first step in the arc-flash hazard analysis. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
00939994
Volume :
50
Issue :
3
Database :
Academic Search Index
Journal :
IEEE Transactions on Industry Applications
Publication Type :
Academic Journal
Accession number :
96119604
Full Text :
https://doi.org/10.1109/TIA.2013.2288416