Back to Search Start Over

Statistical Analyses of Pst and \DeltaV10 Recorded at Electric Arc Furnaces.

Authors :
Hsu, Yu-Jen
Lu, Chan-Nan
Source :
IEEE Transactions on Power Delivery. Jun2014, Vol. 29 Issue 3, p1508-1510. 3p.
Publication Year :
2014

Abstract

Adoption of the IEC flicker standard by IEEE would encourage countries currently using \DeltaV10 flicker standard to consider either updating the \DeltaV10 calculation to make it more suitable for modern day applications, or switching to the IEC standard. In the process of revising the flicker standard, the design of flicker planning level is important. For this purpose, this letter presents comparative statistical analyses of flicker measurements based on present Pst and \DeltaV10 standards. Besides the comparison of synchronous flicker severity indices in 10-min intervals, analyses are also conducted using daily flicker statistical reference values measured at the point of common coupling (PCC) of ac and dc electric arc furnace facilities. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
29
Issue :
3
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
96209099
Full Text :
https://doi.org/10.1109/TPWRD.2013.2280931