Back to Search Start Over

Testing and Enhancement of the Dynamic Performance of a Phasor Measurement Unit.

Authors :
Gurusinghe, Dinesh Rangana
Rajapakse, Athula D.
Narendra, Krish
Source :
IEEE Transactions on Power Delivery. Oct2014, Vol. 29 Issue 4, p1551-1560. 10p.
Publication Year :
2014

Abstract

Phasor measurement units (PMUs) provide the basis for synchrophasor measurements, which are good data sources for capturing power system dynamic behavior. The recently published IEEE Standard C37.118.1-2011 characterizes the dynamic performance of synchrophasor measurements with two performance class filters: P-class and M-class. Practical implementation of a PMU to meet all dynamic requirements is a challenging task. Performance of an actual PMU with the proposed reference performance class filters is presented with a brief overview of the PMU performance evaluation process and the sources of errors in the test environment. Based on the test results, some inadequacies in the reference M-class filter algorithm provided in the standard are revealed, and several minor inconsistencies in the error limits imposed by the standard are highlighted. Finally, some modifications to the M-class reference filter and suggestions to rectify the minor issues in the new standard are proposed. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
29
Issue :
4
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
97237560
Full Text :
https://doi.org/10.1109/TPWRD.2014.2322516