Abstract
- This paper proposes an optimal power flow (OPF) model with flexible AC transmission system (FACTS) devices to minimize wind power spillage. The uncertain wind power production is modeled through a set of scenarios. Once the balancing market is cleared, and the final values of active power productions and consumptions are assigned, the proposed model is used by the system operator to determine optimal reactive power outputs of generating units, voltage magnitude and angles of buses, deployed reserves, and optimal setting of FACTS devices. This system operator tool is formulated as a two-stage stochastic programming model, whose first-stage describes decisions prior to uncertainty realization, and whose second-stage represents the operating conditions involving wind scenarios. Numerical results from a case study based on the IEEE RTS demonstrate the usefulness of the proposed tool. [ABSTRACT FROM PUBLISHER]