Back to Search Start Over

Site Selection Strategy of Single-Frequency Tuned R-APF for Background Harmonic Voltage Damping in Power Systems.

Authors :
Xiaofeng Sun
Jian Zeng
Zhe Chen
Source :
IEEE Transactions on Power Electronics; Jan2013, Vol. 28 Issue 1, p135-143, 9p
Publication Year :
2013

Abstract

Series resonance between capacitance and line inductance may magnify background harmonic voltage and worsen the harmonic voltage distortion in power systems. To solve this problem, in this paper, the transmission line theory is used to set up the distributed parameter model of power system feeders, and analyze the harmonic voltage propagation caused by the background harmonic voltage in power systems. Then, a new strategy is proposed for the site selection of resistive active power filter to damp the background harmonic voltage in power systems. Experiments have been performed to verify the theoretical analysis and demonstrate the effectiveness of the proposed strategy. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858993
Volume :
28
Issue :
1
Database :
Complementary Index
Journal :
IEEE Transactions on Power Electronics
Publication Type :
Academic Journal
Accession number :
101265105
Full Text :
https://doi.org/10.1109/TPEL.2011.2179121