Stray voltages have always been a concern to utility companies and customers. But methods to troubleshoot and monitor nonroutine stray voltage problems are very limited. This paper presents a passive, measurement-based method to identify the contributors to the common cause of stray voltages, the neutral-to-earth voltage (NEV) rise at the service entrance point. The paper shows that the NEV can be decoupled into two components: those related to the customer under investigation and those outside the customer facility. A method to quantify the relative contributions of the two components is proposed. A new concept called current return ratio is introduced to facilitate the decoupling and to quantify the grounding conditions of the system. This paper presents the background, circuit model, concept, and theory of the proposed method. [ABSTRACT FROM AUTHOR]