Back to Search Start Over

Identification of Weak Areas of Network Based on Exposure to Voltage Sagsā€”Part II: Assessment of Network Performance Using Sag Severity Index.

Authors :
Liao, Huilian
Abdelrahman, Sami
Guo, Yue
Milanovic, Jovica V.
Source :
IEEE Transactions on Power Delivery; Dec2015, Vol. 30 Issue 6, p2401-2409, 9p
Publication Year :
2015

Abstract

This paper presents a new stochastic approach to the comprehensive assessment of the impact of voltage sags on large-scale power networks. The approach takes into account the stochastic nature of power system operation, including load variation, uncertainty of fault clearing time by protection relays, fault rates of network components, and the variation/uncertainty in equipment sensitivity to voltage sags. A new duration zone division method is used to derive sag duration and occurrence frequency based on the stochastic distribution of clearing time required by specific protection systems. The adopted probabilistic representation facilitates estimation of network performance based on a single-event characteristic, sag severity index (SSI), developed in the companion paper (Part I). Based on SSI, a new single-site index with respect to voltage sags (bus performance index BPI^S) is developed to comprehensively represent the overall bus performance with respect to voltage sags. The index is used to identify the areas of the network, called weak areas of the network in this paper, containing buses that are most exposed to potentially disruptive voltage sags. The application, robustness, and sensitivity of BPI^S are thoroughly analyzed and discussed in the paper. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858977
Volume :
30
Issue :
6
Database :
Complementary Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
111152877
Full Text :
https://doi.org/10.1109/TPWRD.2014.2362957