Back to Search Start Over

Measurement-Based Real-Time Voltage Stability Monitoring for Load Areas.

Authors :
Hu, Fengkai
Sun, Kai
Del Rosso, Alberto
Farantatos, Evangelos
Bhatt, Navin
Source :
IEEE Transactions on Power Systems; Jul2016, Vol. 31 Issue 4, p2787-2798, 12p
Publication Year :
2016

Abstract

This paper proposes a measurement-based voltage stability monitoring method for a load area fed by N tie lines. Compared to a traditional Thevenin equivalent based method, the new method adopts an N+1 buses equivalent system so as to model and monitor individual tie lines. For each tie line, the method solves the power transfer limit against voltage instability analytically as a function of all parameters of that equivalent, which are online identified from real-time synchronized measurements on boundary buses of the load area. Thus, this new method can directly calculate the real-time power transfer limit on each tie line. The method is first compared with a Thevenin equivalent based method using a 4-bus test system and then demonstrated by case studies on the Northeast Power Coordinating Council (NPCC) 48-machine, 140-bus power system. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858950
Volume :
31
Issue :
4
Database :
Complementary Index
Journal :
IEEE Transactions on Power Systems
Publication Type :
Academic Journal
Accession number :
115245719
Full Text :
https://doi.org/10.1109/TPWRS.2015.2477080