Back to Search Start Over

Probabilistic Assessment and Evaluation of Transients in a Medium-Voltage Three-Phase Capacitor Bank Energized by Unsynchronized Vacuum Switchgears.

Authors :
Machado, Alysson Augusto Pereira
Antunes, Helio Marcos Andre
Pires, Igor Amariz
Silva, Sidelmo Magalhaes
de Jesus Cardoso Filho, Braz
Source :
IEEE Transactions on Industry Applications; Mar/Apr2017, Vol. 53 Issue 2, p918-928, 11p
Publication Year :
2017

Abstract

This paper presents a case study of a medium-voltage three-phase capacitor bank (CB) energization, based on an unsynchronized switching scheme using three independent pole vacuum switches simultaneously commanded. The motivations are cost reduction and simplification of the switching scheme. The maximum current and voltage peaks during transients caused by connection of CB with three independent pole switches or a three-phase mechanically coupled switch are compared. A probabilistic assessment for the overcurrents and overvoltages based on Monte Carlo simulation is also performed. The obtained results show that three single-phase unsynchronized switches could be used in a CB, with good transitory response. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
00939994
Volume :
53
Issue :
2
Database :
Complementary Index
Journal :
IEEE Transactions on Industry Applications
Publication Type :
Academic Journal
Accession number :
122015341
Full Text :
https://doi.org/10.1109/TIA.2016.2631137