Back to Search Start Over

Analysis and Enhanced Control of Hybrid-MMC-Based HVDC Systems During Asymmetrical DC Voltage Faults.

Authors :
Hu, Jiabing
Xu, Kecheng
Lin, Lei
Zeng, Rong
Source :
IEEE Transactions on Power Delivery; Jun2017, Vol. 32 Issue 3, p1394-1403, 10p
Publication Year :
2017

Abstract

This paper presents an enhanced control for HVDC systems employing hybrid modular multilevel converters (MMCs) during asymmetrical dc voltage faults. The characteristics of pole-to-ground (PTG) fault under different system grounding schemes are analyzed. Then, the principle of enhanced control strategy to deal with the PTG fault is presented for a hybrid-MMC-based HVDC system with symmetrical monopolar configuration. A new control variable is proposed on the arm voltages to distribute the power transmitted from the ac side between the upper and lower arms. By adopting the enhanced control, the overvoltage and the fault current can be eliminated when a PTG fault occurs. Furthermore, the hybrid-MMC-based HVDC system can operate continuously with adjustable active power and controllable reactive power by controlling the upper and lower arms of the converter asymmetrically during a fault period. Finally, the feasibility of the proposed control scheme is verified by simulation results in PSCAD/EMTDC. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858977
Volume :
32
Issue :
3
Database :
Complementary Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
122903854
Full Text :
https://doi.org/10.1109/TPWRD.2016.2568240