Back to Search Start Over

Diagnosis Criterion of Abnormality of Transformer Winding by Frequency Response Analysis (FRA).

Authors :
MIYAZAKI, SATORU
MIZUTANI, YOSHINOBU
TAGUCHI, AKIRA
MURAKAMI, JUNICHI
TSUJI, NAOKAZU
TAKASHIMA, MASAHIRO
KATO, OSAMU
Source :
Electrical Engineering in Japan; Nov2017, Vol. 201 Issue 3, p25-34, 10p, 5 Charts, 7 Graphs
Publication Year :
2017

Abstract

SUMMARY Frequency response analysis (FRA) is a powerful technique to detect internal abnormalities within power transformers. However, diagnosis criteria of power transformers by FRA have not been fully established yet. In this paper, a new evaluation method of degree of identification between two transfer functions is proposed. In the proposed method, a frequency window is employed and cross-correlation factor is calculated with moving the window. Furthermore, the proposed method is applied to transfer functions of real transformers with or without some abnormalities. Based on this discussion, objective criteria for diagnosis of abnormalities of transformer windings by FRA are proposed. The proposed criteria are based on a few data of transformers with some abnormalities. Therefore, the proposed criteria are tentative and they would be improved by accumulation of further data. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
04247760
Volume :
201
Issue :
3
Database :
Complementary Index
Journal :
Electrical Engineering in Japan
Publication Type :
Academic Journal
Accession number :
124203624
Full Text :
https://doi.org/10.1002/eej.23012