Back to Search Start Over

Calculation of Touch Voltage Based on Physical Distribution of Earth Fault Current.

Authors :
Stanisic, Stevan
Radakovic, Zoran
Source :
IEEE Transactions on Power Delivery; Oct2017, Vol. 32 Issue 5, p2246-2254, 9p
Publication Year :
2017

Abstract

In this paper, the finite-elements method was used to analyze the approximation being typically used in the international standards for the calculation of the touch voltage, appearing at earth faults in power networks. The calculations in this paper were performed on the series of earthing systems applied in practice and the results are compared with the results of the widely accepted approximate method from standards. The origin of discrepancy in the results is analyzed and evaluated. The outcome of this paper is the justification of the application of Thevenin's theorem and the development of the higher accuracy equations for the resistance between feet and remote earth in case of the application of high resistivity additional surface material. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858977
Volume :
32
Issue :
5
Database :
Complementary Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
124835529
Full Text :
https://doi.org/10.1109/TPWRD.2016.2618062