Reference voltage calculation method based on zero-sequence component optimisation for a regional compensation DVR.
- Source :
- International Journal of Electronics; Apr2018, Vol. 105 Issue 4, p659-678, 20p
- Publication Year :
- 2018
-
Abstract
- This paper describes the design of a dynamic voltage restorer (DVR) that can simultaneously protect several sensitive loads from voltage sags in a region of an MV distribution network. A novel reference voltage calculation method based on zero-sequence voltage optimisation is proposed for this DVR to optimise cost-effectiveness in compensation of voltage sags with different characteristics in an ungrounded neutral system. Based on a detailed analysis of the characteristics of voltage sags caused by different types of faults and the effect of the wiring mode of the transformer on these characteristics, the optimisation target of the reference voltage calculation is presented with several constraints. The reference voltages under all types of voltage sags are calculated by optimising the zero-sequence component, which can reduce the degree of swell in the phase-to-ground voltage after compensation to the maximum extent and can improve the symmetry degree of the output voltages of the DVR, thereby effectively increasing the compensation ability. The validity and effectiveness of the proposed method are verified by simulation and experimental results. [ABSTRACT FROM PUBLISHER]
Details
- Language :
- English
- ISSN :
- 00207217
- Volume :
- 105
- Issue :
- 4
- Database :
- Complementary Index
- Journal :
- International Journal of Electronics
- Publication Type :
- Academic Journal
- Accession number :
- 127184963
- Full Text :
- https://doi.org/10.1080/00207217.2017.1382008