Back to Search Start Over

Evaluation of Low-Power Instrument Transformers for Generator Differential Protection.

Authors :
Normandeau, Michel
Mahseredjian, Jean
Source :
IEEE Transactions on Power Delivery; Jun2018, Vol. 33 Issue 3, p1143-1152, 10p
Publication Year :
2018

Abstract

In hydroelectric power plants, which are characterized by particularly high short-circuit current levels and high time constants, conventional current transformer specifications can result in increased equipment dimensions, thus complicating their installation, especially during refurbishment projects. This paper presents a study to assess the potential of various low-power instrument transformers (LPITs) for generator protection applications. Two types of LPITs were evaluated: the optical current transformer (OCT) and the stand alone merging unit (SAMU). To test the OCT, a 65-kA-peak test source was developed using a real-time simulator. This source was used to inject symmetrical and asymmetrical currents into LPITs for the assessment of protection accuracy class. Low-current tests were also performed to assess their metering classes. This paper presents the design of a high-current test bench, measurement uncertainty analysis, and analysis algorithms used for device evaluation. Analysis results are then presented and discussed in terms of their applicability to generator differential protection using SAMUs and OCTs. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
33
Issue :
3
Database :
Complementary Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
129088092
Full Text :
https://doi.org/10.1109/TPWRD.2017.2745899