Back to Search Start Over

Study on energy-saving design and operation of hospital purification air conditioning system.

Authors :
Chen, Yunyu
Source :
International Journal of Low Carbon Technologies; Jun2018, Vol. 13 Issue 2, p184-190, 7p
Publication Year :
2018

Abstract

In order to ensure the cleanliness of operating room, clean air conditioners are installed in the clean operation departments in hospitals in China. Purification air conditioning system is an air conditioning system with a special function that ensures the cleanliness of the operating room and the required temperature and humidity in the operating room to avoid infection. This paper took the energy-saving design of the clean air-conditioning system of the clean operation department of the First Affiliated Hospital of Wenzhou Medical College, Zhejiang, China, as an example to illustrate the energy-saving methods such as layout optimization, air-conditioning division, secondary return air setting and operation mode adjustment. The energy consumption of primary return air technology and secondary return air technology was calculated. The results showed that energy-saving design could save nearly one-third of energy, improve the level of air-conditioning operation and management, reduce costs, and improve resource utilization, which is of great significance to social development. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
17481317
Volume :
13
Issue :
2
Database :
Complementary Index
Journal :
International Journal of Low Carbon Technologies
Publication Type :
Academic Journal
Accession number :
129502011
Full Text :
https://doi.org/10.1093/ijlct/cty013