Back to Search Start Over

Analysis of Single-Phase-to-Ground Faults at the Valve-Side of HB-MMCs in HVDC Systems.

Authors :
Li, Gen
Liang, Jun
Ma, Fan
Ugalde-Loo, Carlos E.
Liang, Haifeng
Source :
IEEE Transactions on Industrial Electronics; Mar2019, Vol. 66 Issue 3, p2444-2453, 10p
Publication Year :
2019

Abstract

Although the probability of occurrence of station internal ac grounding faults in modular multilevel converter (MMC)-based high-voltage direct-current systems is low, they may lead to severe consequences that should be considered when designing protection systems. This paper analyzes the characteristics of valve-side single-phase-to-ground (SPG) faults in three configurations of MMC systems. Fault responses for symmetrical monopole MMCs are first studied. Upper arm overvoltages and ac-side nonzero-crossing currents arising from SPG faults in asymmetrical and bipolar configurations are then investigated. DC grounding using an LR parallel circuit is employed to create current zero-crossings, which will enable the operation of grid-side ac circuit breakers. The theoretical analysis is verified through simulations performed in PSCAD/EMTDC, with simulation results and the theoretical analysis showing a good agreement. The studies in this paper will be valuable for the design of protection systems for station internal ac grounding faults. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
02780046
Volume :
66
Issue :
3
Database :
Complementary Index
Journal :
IEEE Transactions on Industrial Electronics
Publication Type :
Academic Journal
Accession number :
132807522
Full Text :
https://doi.org/10.1109/TIE.2018.2829666