Back to Search Start Over

Integrated Noncontact Diagnostics of the Operable Condition of High-Voltage Insulators.

Authors :
Golenishchev-Kutuzov, A. V.
Golenishchev-Kutuzov, V. A.
Ivanov, D. A.
Mardanov, G. D.
Semennikov, A. V.
Source :
Russian Journal of Nondestructive Testing; Aug2019, Vol. 55 Issue 8, p596-602, 7p
Publication Year :
2019

Abstract

We investigated the features of defects on the rod and the "rod–end-terminal" contact of polymer and porcelain insulators using the developed integrated method for noncontact remote diagnostics of the performance of high-voltage insulators, including the initial detection of local areas with elevated electric-field gradients and the measurement of the set of characteristics of partial discharges. The emission of extra-large partial discharges was discovered, and their features were studied. Based on the measurement results, a diagram was constructed for electrophysical processes accompanying the emission of extra-large partial discharges, and their causes were established. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
10618309
Volume :
55
Issue :
8
Database :
Complementary Index
Journal :
Russian Journal of Nondestructive Testing
Publication Type :
Academic Journal
Accession number :
139315583
Full Text :
https://doi.org/10.1134/S1061830919080060