Back to Search Start Over

Autonomous Model Predictive Controlled Smart Inverter With Proactive Grid Fault Ride-Through Capability.

Authors :
Easley, Mitchell
Jain, Sarthak
Shadmand, Mohammad
Abu-Rub, Haitham
Source :
IEEE Transactions on Energy Conversion; Dec2020, Vol. 35 Issue 4, p1825-1836, 12p
Publication Year :
2020

Abstract

This article presents an autonomous model predictive controlled smart photovoltaic (PV) inverter with proactive grid fault-ride through capability. The proposed smart inverter control features decoupled active and reactive power. It can seamlessly switch between the anticipated modes of operation based on grid condition or grid operator command. The smart inverter autonomously adjusts its active and reactive power set-points according to the grid condition, it operates in maximum power point tracking (MPPT) and low voltage ride through (LVRT) modes in normal grid and faulty grid condition modes, respectively. The proposed novel autonomous model predictive control (AMPC) scheme is leveraged to enhance the operation of the smart inverter. The AMPC includes online weight factor auto-tuning and control objective normalization to eliminate the required trial-and-error weight factor design stage in conventional model predictive control. This feature is particularly beneficial to the dual-mode smart inverter operation. The performance of the proposed grid-tied smart inverter based on the AMPC is verified experimentally. The results demonstrate that the proposed AMPC-based smart inverter features robust grid fault detection, autonomous adjustment of active and reactive power set-points, seamless transition between modes of operation, and elimination of controller tuning effort. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858969
Volume :
35
Issue :
4
Database :
Complementary Index
Journal :
IEEE Transactions on Energy Conversion
Publication Type :
Academic Journal
Accession number :
147292005
Full Text :
https://doi.org/10.1109/TEC.2020.2998501