Back to Search Start Over

Optimal operation of PV‐DG‐battery based microgrid with power quality conditioner.

Authors :
Jha, Shatakshi
Hussain, Ikhlaq
Singh, Bhim
Mishra, Sukumar
Source :
IET Renewable Power Generation (Wiley-Blackwell); Feb2019, Vol. 13 Issue 2, p418-426, 9p
Publication Year :
2019

Abstract

This study presents an optimal control operation of a photovoltaic‐battery based standalone microgrid, feeding non‐linear loads. To ensure continuous power supply to the critical loads during low insolation or low battery state of charge, a diesel generator (DG) is used as an auxiliary generator. This cost effective hybrid system with maximum utilisation of the renewable as well as fossil fuel based generators can be employed in hospitals, telecom stations in remote areas. In order to nullify the effect of non‐linear loads on the DG, modified enhanced phase‐locked loop (EPLL) based power quality conditioner is used. The characteristic equation of conventional EPLL is amplitude dependent, thus, the controller tuning parameters need to be modified if the input signal varies over a large range. The presented controller overcomes this problem making the system more robust in eliminating noise and harmonics and extracting fundamental component of a given signal. This component is drawn from the DG with the help of a voltage source converter, thus, making its current always distortion free. The proposed control scheme is simulated in MATLAB. Furthermore, experimental verification is done on a laboratory prototype of the same. The steady state and dynamic responses of the system validate its satisfactory performance. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
17521416
Volume :
13
Issue :
2
Database :
Complementary Index
Journal :
IET Renewable Power Generation (Wiley-Blackwell)
Publication Type :
Academic Journal
Accession number :
148144749
Full Text :
https://doi.org/10.1049/iet-rpg.2018.5648