Back to Search
Start Over
Fast single-end line protection method for the meshed multi-terminal HVDC grid.
- Source :
- Journal of Engineering; Apr2019, Vol. 2019 Issue 4, p1602-1606, 5p
- Publication Year :
- 2019
-
Abstract
- In view of the short-circuit fault characteristics, the protection technique of the dc lines limits the development of the modular multi-level converter (MMC)-based HVDC grid in a large extent. This study derives the calculation formulas of the transient voltages of internal and external faults and proposes a single-end protection scheme based on the transition period (TP) from the abrupt changing point to the first extreme point of the fault voltage. Due to the current-limiting reactors, the TP of the internal fault is much shorter than that of the external fault, which is used to discriminate internal fault from external fault. A four-terminal symmetrical bipolar HVDC grid based on MMC is modelled using PSCAD/EMTDC, and simulation results demonstrate the validity of the new proposed dc transmission line protection method. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 20513305
- Volume :
- 2019
- Issue :
- 4
- Database :
- Complementary Index
- Journal :
- Journal of Engineering
- Publication Type :
- Academic Journal
- Accession number :
- 148148371
- Full Text :
- https://doi.org/10.1049/joe.2018.8722