Back to Search Start Over

Time-Domain Protection and Fault Location of Wye-Connected Shunt Capacitor Banks Using Superimposed Current and Differential Voltage.

Authors :
Mohanty, Rabindra
Pradhan, Ashok Kumar
Source :
IEEE Transactions on Power Delivery; Dec2021, Vol. 36 Issue 6, p3486-3495, 10p
Publication Year :
2021

Abstract

This paper presents protection and fault location of wye-connected shunt capacitor banks used in medium or high voltage applications. The proposed method is sensitive to single element failure obtained by using voltage adaptive instantaneous superimposed current in each phase. The change in equivalent reactance computed using time-domain signals is used to find the number of failed capacitor element and types of fault. The location of the faulted capacitor is identified using sign of the voltage difference of the lower and upper halves of the shunt capacitor bank. The performance of the proposed method is tested for various cases including identical faults, simultaneous faults, system voltage unbalance in both single and double wye-connected shunt capacitor banks. The method is also validated using field data collected from a 400 kV SCB for an internal fault. The proposed technique is compared with available methods and found accurate. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
36
Issue :
6
Database :
Complementary Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
153854289
Full Text :
https://doi.org/10.1109/TPWRD.2020.3043693